Cabinet Electrical BOM — the box the HBOX lives inside
Source: Selección de componentes para gabinete2.xlsx (Helgen, 2026-06)
Date captured: 2026-06-19
Key point: the HBOX is not mounted bare on a machine — it sits inside an
industrial electrical cabinet (gabinete) with DIN-rail power and protection
components. This BOM is that cabinet. It is productized across voltages (12 /
24 / 48 / 110 / 230 V machines) and across multiple port terminals (ICAVE,
Hutchison, TIMSA, EIT, LCT) — i.e. this is heading to hundreds of cabinets, so
the fixes must be production-grade and repeatable. (Pricing/margins omitted here —
see the sheet.)
Nested-enclosure architecture (important for thermal)
Machine power (12/24/48/110/230 V) + ignition
│
▼ ┌──────────────── Gabinete IP67 (ABS, Yetlebox P3901, 39×29×16 cm) ───────────┐
breaker │ DIN rail · terminals · SPD · fuse holder · SSR/opto (ignition sense) │
+ SPD ──►│ Mean Well DDR-60G-24 ──► clean 24 Vdc ─────────────┐ (supply dissipates │
│ │ heat *inside* box) │
│ ┌────────── HBOX (3D-printed ASA, sealed) ────────┼───┐ │
│ │ PowerBoost 1000C + LiPo · simpleRTK2B+4G · STM32 watchdog │ │
│ └───────────────────────────────────────────────────┘ │
└───────────────────────────────────────────────────────────────────────────┘
Two sealed boxes, one inside the other, with a 60 W-class power supply generating
heat in the outer one, in full sun. See the thermal note in
03-Architecture-Hardware/hardware-respec-and-pcb-brief.md §thermal.
Cabinet catalog (Helgen final selection, by machine voltage)
| Function | 12 V | 24 V | 48 V | 110–230 V |
|---|---|---|---|---|
| Enclosure (IP67, ABS) | Yetlebox P3901 | P3901 | P3901 | P3901 |
| DIN rail | Weidmüller TS 35×7.5 | ← | ← | ← |
| Neutral terminals ×5 | Weidmüller WDU 2.5 PA/VI | ← | ← | ← |
| Ground terminals | Weidmüller WPE4 | ← | ← | ← |
| Fuse-holder terminal ×3 | Phoenix Contact 3212166 PT 6-FSI/C (blade) | ← | ← | ← |
| Ignition isolation (SSR / opto) | Weidmüller MOS 12-28VDC | Weidmüller TOS 24VDC 2A | Wago 859-744 | IDEC RV8S-L-D24-A120 |
| Surge protection (SPD) | Phoenix TTC-6-TVSD-C-12DC-PT-I | …-24DC- | …-48DC- | Phoenix DC + Total Ground A2021 (AC) |
| Breaker | Phoenix TMC 81C 05A (5 A) | ← | ← | Schneider A9F74202 (2 A, AC) |
| Power supply → 24 Vdc | Mean Well DDR-60G-24 | Mean Well DDR-60G-24 | Mean Well DDR-60L-24 | Siemens 6EP1332-1LB00 (SITOP) |
Output rail in all cases: 24 Vdc, ~2.4 A, 60 W.
What this means for the fix (engineering read)
- The cabinet's power & protection are already industrial-grade. Surge suppression (Phoenix TVS/SPD), a breaker, isolated ignition sensing (SSR/opto), and a quality regulated supply (Mean Well / Siemens) are present at the cabinet level. The HBOX PCB does NOT need to re-implement input surge/breaker — it can assume a clean 24 Vdc feed and an isolated ignition signal. That simplifies the HBOX redesign (see hardware brief).
- So the weak link is confirmed to be inside the HBOX, exactly where the client pointed: PowerBoost 1000C + LiPo + Dupont — not the cabinet (the ASA enclosure is adequate). The HBOX-internal job is 24 V → 5 V (robust buck) + watchdog + the RTK stack, with the LiPo decision (drop/replace) still open.
- Verify the actual fuse value. The PT 6-FSI/C is a holder; the fitted blade fuse rating is what matters for the client's "under-rated fuse" concern — read the installed fuse and compare to the measured worst-case + inrush.
- The Mean Well runs hot inside a sealed box. At 60 W class it dissipates several watts continuously; that heat has nowhere to go in a sealed ABS IP67 cabinet → it raises the ambient the HBOX (and its 18650 + boost + modem) must survive. This is now a primary thermal driver, not just solar load.
Open question for Leo to confirm: does the HBOX receive the cabinet's 24 V (then step down internally), or the raw machine voltage? The BOM implies a clean 24 V feed + isolated ignition — confirm so the HBOX power redesign targets the right input.